NCS-TT106 Temperature Transmitter

  • NCS-TT106 Temperature Transmitter
  • NCS-TT106 Temperature Transmitter
  • NCS-TT106 Temperature Transmitter
  • NCS-TT106 Temperature Transmitter
  • video
NCS-TT106 Temperature Transmitter
  • Microcyber
  • Liaoning, China
  • In Stock
  • 500 Sets/Month

NCS-TT106 temperature transmitter supports FF H1(Foundation Fieldbus) HART and Profibus PA protocoIs and multiple temperature sensors. With independent R&D communication controller, it has become a fieldbus temperature transmitter with high performance.
1. Support 4 types of thermal resistance and 8 types of thermocouple
2. Thermal resistance supports 2-wire, 3-wire and 4-wire
3. The cold junction compensation accuracy of thermocouple can reach ±0.15 ℃
4. High precision (better than grade 0.1), low temperature drift (better than ±50ppm/℃ )
5. FCG interoperability test certification (ITK 6) and PNO interoperability test certification (PA profile 3.02), comply with HART 7
6. CE, explosion-proof (intrinsically safe, flameproof) certification

Overview


NCS-TT106F intelligent temperature transmitter adopts field bus technology, is a new generation of intelligent temperature transmitter, is an indispensable field device in process control. The device integrates a wealth of functional modules, which can achieve both general detection functions and complex control strategies.


NCS-TT106F adopts digital technology and can be applied to a variety of thermal resistance and thermocouple sensors. It has a wide measuring range and a simple interface between the field and the control room.


NCS-TT106F series intelligent temperature transmitter supports Foundation Fieldbus protocol, which can be widely used in petroleum, chemical, electric power, metallurgy and other industries.


Temperature transmitter installation

Dimensions

NCS-TT106 Temperature Transmitter


Installation

Via positioning hole, use two screws to install the temperature module to temperature housing or rail.


Temperature Transmitter


Wiring

NCS-TT106

The power supply of NCS-TT106F temperature transmitter and bus signal share a pair of cables, called bus cable. It is recommended to use the fieldbus dedicated cable recommended by IEC61158-2. The signal cable and bus cable should not share the conduit or open channel with the power cables of other equipment, and should be far away from high-power equipment. The shielded wires at both ends of the bus are grounded by single-ended grounding.


Technical specifications

Basic parameters

Bus interface

FOUNDATION FIELDBUS

Bus power

9~32VDC

9~17.5VDC(Intrinsically safe)

Input signal

Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω resistance;

B E J K N R S T thermocouple、-100mV~100mV、Custom defined TC、Custom defined RTD

Number of channels

Single channel

RTD wiring

2-wire、3-wire、4-wire

Update time

0.5s

Operating temperature

-40~85℃

Storage temperature

-40~85℃

Humidity range

5~95%RH

Electrical isolation

1000VAC

Voltage effect

±0.005%/V

Protection level

Terminal IP00 ;Housing IP40

Explosion-proof

Ex ia IIC T4 Ga

EMC

GB/T 18268.1-2010 Immunity requirements for industrial sites in "Electromagnetic Compatibility Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use Part 1: General Requirements"

GB/T 18268.25-2010 "Electromagnetic compatibility requirements for electrical equipment for measurement, control and laboratory use-Part 25: Special requirements. Test configuration, working conditions and performance criteria for field devices whose interfaces conform to IEC 61784-1, CP 3/2"


Thermal resistance technical index

RTD Normal temperature accuracy index(25

Signal type

Recommended range(

Accuracy

Temperature drift (per )

Resistance signal

0~500Ω

±0.04Ω

±0.001Ω

0~ 4000Ω

±0.35Ω

±0.015Ω

PT100

-200~850℃

±0.15℃

±0.003℃

PT1000

-200~850℃

±0.15℃

±0.005℃

CU50

-50~150℃

±0.15℃

±0.005℃

CU100

-50~150℃

±0.10℃

±0.003℃

 

RTD Other technical indicators

Wiring

2、3、4

Common mode rejection ratio

≥70dB(50Hz & 60HZ)

Differential mode rejection ratio

≥70dB(50Hz & 60HZ)

 

Thermocouple technical indicators

Thermocouple room temperature accuracy index(25

Signal type

Range

Recommended range

Accuracy

Temperature drift (per )

mV

-100mV~+100mV

-100mV~+100mV

±0.025mV

±0.001 mV

B

0℃~1820℃

500℃~1810℃

±0.77℃

±0.050℃

E

-270℃~1000℃

-200℃~1000℃

±0.20℃

±0.025℃

J

-210℃~1200℃

-190℃~1200℃

±0.35℃

±0.01℃

K

-270℃~1372℃

-200℃~1372℃

±0.40℃

±0.025℃

N

-270℃~1300℃

-190℃~1300℃

±0.50℃

±0.015℃

R

-50℃~1768℃

0℃~1768℃

±0.75℃

±0.023℃

S

-50℃~1768℃

0℃~1768℃

±0.70℃

±0.023℃

T

-270℃~400℃

-200℃~400℃

±0.35℃

±0.015℃


 Other technical indicators of thermocouple

Compensation accuracy

±0.5℃

Sensor type

B,E,J,N,K,R,S,T;-100mV~+100mV Voltage

Common mode rejection ratio

≥70dB(50Hz & 60HZ)

Differential mode rejection ratio

≥70dB(50Hz & 60HZ)


Physical characteristics

Size

NCS-TT106F:¢45*23mm;NCS-TT106F-R1:110*99*22.5mm

Housing material

Nylon


Application

NCS-TT106 Temperature Transmitter

Certificates

Temperature Transmitter


FAQ

Q: What’s Temperature Transmitter 2-wire zero point calibration configuration?

A: For 2-wire measurement, 2-wire zero point calibration can be realized by modifying transducer block TWO_WIRES_COMPENSATION parameter.

 

Q: Can I get the electronic manual?

A: Yes, please contact us.

 

Q: What type of cable should I use for wiring?

A: Fieldbus temperature module’s power and bus signal share a pair of cable, and it is called bus cable. It is suggested the user use fieldbus special cable recommended by IEC61158-2.

 

Q: Can you provided OEM service?

A: Yes, we can, such as communication board, we can also provided fieldbus development toolkit.


Hot Products

NCS-TT106NCS-TT106 Temperature Transmitter




Factory Show
Factory Show
Quality Control
Quality Control
Mail consultation
Please feel free to give your inquiry in the form below. We will reply you in 24 hours.
close left right