NCS-TT106 Head Mounted Temperature Transmitter

  • Sales NCS-TT106 Head Mounted Temperature Transmitter, Buy NCS-TT106 Head Mounted Temperature Transmitter, NCS-TT106 Head Mounted Temperature Transmitter Factory, NCS-TT106 Head Mounted Temperature Transmitter Brands
  • Sales NCS-TT106 Head Mounted Temperature Transmitter, Buy NCS-TT106 Head Mounted Temperature Transmitter, NCS-TT106 Head Mounted Temperature Transmitter Factory, NCS-TT106 Head Mounted Temperature Transmitter Brands
  • video
NCS-TT106 Head Mounted Temperature Transmitter
  • Microcyber
  • Liaoning, China
  • In Stock
  • 500 Sets/Month

NCS-TT106 temperature transmitter supports FF H1(Foundation Fieldbus) HART and Profibus PA protocoIs and multiple temperature sensors. With independent R&D communication controller, it has become a fieldbus temperature transmitter with high performance.

Description


NCS-TT106 smart temperature module, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT106 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.

 

NCS Series of Intelligent Transmitters are digital, intelligent, network-based, merged with advanced, reliable and stable sensor technology, to be designed as a new generation of Fieldbus Intelligent Transmitter.

 

NCS Series of Intelligent Transmitter have been designed with high precision and high reliability, high stability. The pressure, temperature, currents and other physical quantities are displayed on LCD module. Zero drift, range settings and many other functions, are realized by the magnetism bar operation. The interoperability between different systems and equipments are realized by the Equipment Description Document, which is compatible to a variety of device management software, and adapting to harsh electromagnetic environment. NCS Series of Intelligent Transmitter have been used in inflammable and explosive places according to Intrinsically Safety Design.

NCS-TT106 uses digital technology, so it can connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.



Features


Support multiple thermal resistances and thermocouples

Thermal resistance supports 2/3/4-wire connection mode

Thermocouple can use cold end compensation function


Parameters


NCS-TT106H  HART

Input Signal

Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω

B,E,J,N,K,R,S,T eight kinds of Thermocouple

-100mV~100mV voltage signal

Channel

Single

RTD Wiring

2-wire, 3-wire, 4-wire

Bus Power

HART: 11~35 VDC  

Bus Signal

HART,current mode

Electric isolation

1000VAC

Working Temperature

-40℃~85

Humidity Range

5%~95%RH

Start Time

≤5s

Refresh Time

0.5s

EMC

GB/T 18268.1-2010

Protection

Terminal IP00, housing IP40

Voltage effect

±0.005%/V

Alarm signal

Alarm output can be set as   3.5…23 mA

Upper/lower limit current    20.8mA / 3.8mA

Current accuracy

0.03%


RTD Parameter

RTD Parameter at Normal Temperature

Signal type

Suggested range

Accuracy(25

Temperature drift(per

Resistance Signal

0~500Ω

±0.04Ω

±0.001Ω

0~4000Ω

±0.35Ω

±0.015Ω

PT100

-200 ~ 850℃

±0.15℃

±0.003℃

PT1000

-200 ~ 850℃

±0.15℃

±0.005℃

CU50

-50 ~ 150℃

±0.15℃

±0.005℃

CU100

-50~ 150℃

±0.10℃

±0.003℃


Thermocouple

Thermocouple Parameter at Normal Temperature

Signal type

Suggested range

Accuracy(25

Temperature drift(per

mV

-100mV ~ +100mV

±0.025mV

±0.001 mV

B

500 ℃~ 1810℃

±0.77℃

±0.050℃

E

-200 ℃~ 1000℃

±0.20℃

±0.025℃

J

-190 ℃~ 1200℃

±0.35℃

±0.01℃

K

-200℃ ~ 1372℃

±0.40℃

±0.025℃

N

-190℃ ~ 1300℃

±0.50℃

±0.015℃

R

0℃ ~ 1768℃

±0.75℃

±0.023℃

S

0 ℃~ 1768℃

±0.70℃

±0.023℃

T

-200℃ ~ 400℃

±0.35℃

±0.015℃


 NCS-TT106F  Foundation Fieldbus

Bus interface

FF

Bus power

9~32VDC

Input Signal

Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω Resistance;

B E J K N R S T Thermocouple、-100mV~100mV、Custom defined TC、Custom defined RTD

Channel

Single

RTD Wiring

2-wire, 3-wire, 4-wire

Refresh Time

0.5s

Working Temperature

-40~85

Storage temperature

-40~85

Humidity Range

5~95%RH

Electric isolation

1000VAC

Voltage effect

±0.005%/V

Protection

Terminal IP00, housing IP40

EMC

GB/T 18268.1-2010

GB/T 18268.25-2010


RTD Parameter

RTD Parameter at Normal Temperature25℃

Signal type

Suggested range

Accuracy(25

Temperature drift(per

Resistance Signal

0~500Ω

±0.04Ω

±0.001Ω

0~ 4000Ω

±0.35Ω

±0.015Ω

PT100

-200~850℃

±0.15℃

±0.003℃

PT1000

-200~850℃

±0.15℃

±0.005℃

CU50

-50~150℃

±0.15℃

±0.005℃

CU100

-50~150℃

±0.10℃

±0.003℃


Thermocouple

Thermocouple Parameter at Normal Temperature25℃

Signal type

Suggested range

Accuracy(25

Temperature drift(per

mV

-100mV~+100mV

±0.025mV

±0.001 mV

B

500℃~1810℃

±0.77℃

±0.050℃

E

-200℃~1000℃

±0.20℃

±0.025℃

J

-190℃~1200℃

±0.35℃

±0.01℃

K

-200℃~1372℃

±0.40℃

±0.025℃

N

-190℃~1300℃

±0.50℃

±0.015℃

R

0℃~1768℃

±0.75℃

±0.023℃

S

0℃~1768℃

±0.70℃

±0.023℃

T

-200℃~400℃

±0.35℃

±0.015℃


Dimension


head mounted transmitter

Temperature Module Dimension (Unit: mm)


Installation

Via positioning hole, use two screws to install the temperature module to temperature housing or rail.


head mounted temperature transmitter

                            temperature transmitter


Wiring

head mounted transmitter

Fieldbus temperature module’s power and bus signal share a pair of cable, and it is called bus cable. It is suggested the user use fieldbus special cable recommended by IEC61158-2.

 

The signal cable and bus cable cannot share wires or wire slot with other device power wire, and they shall be away from device with high power.

The shielded wires of bus ends shall be connected to the ground.


Application

head mounted temperature transmitter

Certificates

  temperature transmitter


FAQ

Q: What’s Temperature Transmitter 2-wire zero point calibration configuration?

A: For 2-wire measurement, 2-wire zero point calibration can be realized by modifying transducer block TWO_WIRES_COMPENSATION parameter.

 

Q: Can I get the electronic manual?

A: Yes, please contact us.

 

Q: What type of cable should I use for wiring?

A: Fieldbus temperature module’s power and bus signal share a pair of cable, and it is called bus cable. It is suggested the user use fieldbus special cable recommended by IEC61158-2.

 

Q: Can you provided OEM service?

A: Yes, we can, such as communication board, we can also provided fieldbus development toolkit.


Hot Products

head mounted transmitterhead mounted temperature transmittertemperature transmitter



Quality Control
Quality Control
Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right