MODBUS To HART Module/M0310 General Instroduction
Microcyber Corporation has customized many built-in protocol converting modules for the majority of field device manufacturers, supporting to connect MODBUS RTU protocol (hereinafter referred to as “MODBUS” protocol) slave device into a variety of fieldbus system. The function of M0310 built-in MODBUS to HART module (hereinafter referred to as "HART module") is to convert MODBUS slave device into HART slave device.
M1100S WirelessHART Communication Module:
1. Choose low-power chips
2. Comply with HART7.5 standard
3. Pass FCG WirelessHART certification
4. Quickly integrate WirelessHART into existing equipment
5. Safe, reliable and standard data transmission
M0310 General Instroduction
Microcyber Corporation has customized many built-in protocol converting modules for the majority of field device manufacturers, supporting to connect MODBUS RTU protocol (hereinafter referred to as “MODBUS” protocol) slave device into a variety of fieldbus system. The function of M0310 built-in MODBUS to HART module (hereinafter referred to as "HART module") is to convert MODBUS slave device into HART slave device.
M0310 Modbus to HART embedded module is one of the Microcyber M series embedded modules developed by Microcyber Corporation. By embedding M0310 into the user device with Modbus RTU communication capability, the Modbus slave can be transformed into a HART slave.
M0310 Modbus to HART embedded Module:
1. Comply with HART V7.0 protocol standard
2. Comply with standard Modbus RTU protocol
3. Support Modbus communication parameters dynamic configuration
4. Support 6 device variables and 4 dynamic variables
5. M0310-ACT is an actuator-specific version and different from M0310 hardware
M0310 Dimension

M0310 Specification
Measuring Object | Modbus RTU slave device |
Power Supply | (6~42)VDC |
Bus Protocol | 2-wire,(4~20)mA+HART |
Load Resistance | (0~1500) Ω(normal) |
(230~1100) Ω(HART communication) | |
Isolating Voltage | Modbus and HART bus interface,500 VAC |
Temperature Range | (-40~85) ℃ |
Humidity Range | (5~95) %RH |
Start Time | ≤5s |
Refresh Time | 0.2s |
Damp Adjust | Time constant 0~32s |
Output Current Accuracy | Max. error is ≤50 μA |
M0310 Technical Details


M0310 Application
As a general product, HART module must face the different interface characteristics (slave address, communication rate, communication verification method, etc.) and data storage method (data register address, data type, byte order, etc.) of various MODBUS devices, and also end user's requirements for HART dynamic variable allocation (data registers are mapped to device variables, and device variables are mapped to dynamic variables), and these can be reconfigured by the device manufacturer.
WirelessHART industrial products are widely used in process industry to meet the demand of reliable, stable and safe wireless communication. The M wireless communication module, G series gateway and wireless instrument are applicable to various industrial monitoring scenarios and with full set of development kits and technical support services for customers with independent development capability.

M0310 Package and Delivery