Two Channel Temperature Transmitter/NCS-TT105 Temperature Sensor

- :Microcyber
- :Shenyang,China
- :3 Work Days
- :1000Pieces/Month
NCS-TT105 Temperature Transmitter adopts fieldbus technology, is a new generation of fieldbus smart temperature transmitter, and is an indispensable field device in process control. NCS-TT105 smart temperature transmitter supports HART, FF, PA protocol and can be widely used in petroleum, chemical, power plant, metallurgy and other industries.
NCS-TT105 Smart Temperature Transmitter:
1. Support the latest versions of FF H1, PROFIBUS PA and HART protocols
2. Support dual-channel sensor input, support redundancy and hot backup
3. Thermal resistance supports 2-wire, 3-wire and 4-wire
4. The cold end compensation accuracy of thermocouple is ± 1.0℃
5. High precision (better than grade 0.1), low temperature drift (better than ± 50ppm/℃)
6. Enhanced type: ±0.1℃ (Pt100, Pt1000)
Temperature Sensor Product Overview
NCS-TT105 temperature transmitter is a new generation of smart transmitter with FF H1,PROFIBUS PA or HART technology.
NCS-TT105 transmitter integrates abundant function blocks and realizes not only normal measurement function but also complicated control strategy.It uses digital technology, so it can connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
Temperature Sensor Features:
Support multiple thermal resistances and thermocouples
Thermal resistance supports 2/3-wire connection mode
Thermocouple can use cold end compensation function
Temperature Sensor Details:
Temperature Sensor Parameter:
Input Signal | Pt100、Pt1000、PT 200、PT500、CU50、CU100、0~500Ω、 0~4000 Ω; B E J K N R S T thermocouple, -100mV~100mV | |||
RTD Mode of Connection | 2,3,4 wires connection | |||
Power | FF/PA | (9~32)VDC | ||
HART | (11.5~45)VDC | |||
Bus Protocol | (4~20)mA+HART, FF, PA | |||
Channels | 2 channels | |||
Insulation | 1000VAC | |||
Display | LCD display or no display (optional) | |||
Temperature Range | (-40~85) ℃ | (-40~80) ℃ T5 (-40~60) ℃ T6 | (-40~70) ℃ T5 (-40~60) ℃ T6 | |
| Non-Ex | Ex d | Ex ia | |
Humidity Range | (5~95)%RH | |||
Storage Temperature | -40 ~ 85℃ | |||
Start Time | ≤ 5-Second (HART) ≤ 8-Second (FF, PA) | |||
Refresh Time | The 0.8 ~ 1.3s depends on the type and wiring mode of the sensor | |||
Damping Adjustment | Time constant of 0 to 32 seconds | |||
Cold-end Temperature | ±1℃ | |||
Alerting signal (only HART) | The alarm output can be set at 3.5 … 23 mA Upper / lower limit current 20.8mA / 3.7mA | |||
Current accuracy (only HART) | Normal temperature: 0.03% / Temperature drift: ±30ppm | |||
Voltage Influence | ±0.005%/V | |||
Ex Level | Ex db IIC T5/T6 Gb / Ex ia [ia Ga]IIC T4/T6 Ga(HART) |
Temperature Sensor Size :
Temperature Sensor RTD Technical Specification:
Sensor type | Working range (℃) | Accuracy (25℃) | Temperature drift(per°C) |
Resistance | 0~500Ω | ±0.04Ω | ±0.001Ω |
0~4000Ω | ±0.35Ω | ±0.015Ω | |
PT100 | -200 ~ 850℃ | ±0.15℃ | ±0.003℃ |
PT 200 | -200 ~ 850℃ | ±0.15℃ | ±0.005℃ |
PT 500 | -200 ~ 850℃ | ±0.15℃ | ±0.005℃ |
PT1000 | -200 ~ 850℃ | ±0.15℃ | ±0.005℃ |
CU50 | -50 ~ 150℃ | ±0.15℃ | ±0.005℃ |
CU100 | -50~ 150℃ | ±0.10℃ | ±0.003℃ |
FF Smart Temperature Transmitter Configuration:
FF transmitter supports many kinds of connection, as shown.There is a transmitter bus connection; the bus ends are connect terminal matching resistance, which ensures the signal quality, as shown .The maximum length of bus is 1900 meters and it can be prolonged to 10 kilometers with repeaters.
FF network topology
FF bus connection
Temperature Sensor Certification:
Temperature Sensor Packaging &Shipping: