NCS-TT105 Smart Temperature Transmitter

  • NCS-TT105 Smart Temperature Transmitter
  • NCS-TT105 Smart Temperature Transmitter
  • NCS-TT105 Smart Temperature Transmitter
NCS-TT105 Smart Temperature Transmitter
  • Microcyber
  • China
  • In Stock
  • 500 Sets/Month

NCS-TT105 Temperature Transmitter adopts fieldbus technology, is a new generation of fieldbus smart temperature transmitter, and is an indispensable field device in process control. NCS-TT105 smart temperature transmitter supports HART, FF, PA protocol and can be widely used in petroleum, chemical, power plant, metallurgy and other industries.

NCS-TT105 Smart Temperature Transmitter: adopts fieldbus technology, is a new generation of fieldbus smart temperature transmitter, and is an indispensable field device in process control. NCS-TT105 smart temperature transmitter supports HART, FF, PA protocol and can be widely used in petroleum, chemical, power plant, metallurgy and other industries.


NCS-TT105 Smart Temperature Transmitter:

1. Support the latest versions of FF H1, PROFIBUS PA and HART protocols

2. Support 6 types of thermal resistance and 8 types of thermocouple

3. Thermal resistance supports 2-wire, 3-wire and 4-wire

4. The cold end compensation accuracy of thermocouple is ± 1.0℃

5. High precision (better than grade 0.1), low temperature drift (better than ± 50ppm/℃)


NCS-TT105 Temperature Transmitter Size Shown:

hart temperature transmitter

Size(Unit:mm)


NCS-TT105 Temperature Transmitter Wiring Shown:

FF H1 temperature transmitter

PROFIBUS PA temperature transmitter



For two-channel measurements, both channel units must have the same settings (e.g. both temperature units). 


Failure Alarm Setting :

The HART temperature transmitter has a self-diagnostic function. When faults are detected, such as sensor open circuit, sensor short circuit or AD error, the transmitter will automatically output alarm current. The mode of alarm current depends on the setting of fault alarm current dial switch on communication card. When the "AL" dial switch is on the side of OFF, the alarm current is higher than 21.75 mA. When the AL dial switch is on the ON side, the alarm current is <3.7mA.


Configuration protection settings:

 HART temperature transmitter provides dial switch settings for device configuration protection or not. When the configuration protection status is set, the dial switch is transferred to the ON side and the socket card does not allow any operation to change the configuration of the device. Conversely, a dial switch on the OFF side allows configuration changes to be made to the device.


NCS-TT105 Temperature Transmitter technical indicators of thermal power resistance: 

RTD Accuracy (25℃)

Sensor typeWorking range (℃)Accuracy (25℃)Heating drift (per ℃)
Resistance0~500Ω±0.05Ω±0.005Ω
0~4000Ω±0.40Ω±0.04Ω
PT100-200 ~ 850℃±0.20℃±0.01℃
PT50_GOST-200 ~ 850℃±0.20℃±0.01℃
PT100_GOST-200 ~ 850℃±0.20℃±0.01℃
PT200-200 ~ 850℃±0.20℃±0.01℃
PT500-200 ~ 850℃±0.20℃±0.01℃
PT1000-200 ~ 850℃±0.20℃±0.01℃
CU50-50 ~ 150℃±0.20℃±0.005℃
CU50_GOST-180 ~ 200℃±0.20℃±0.005℃
CU100-50 ~ 150℃±0.20℃±0.005℃
CU100_GOST-180 ~ 200℃±0.20℃±0.005℃


NCS-TT105 Temperature Transmitter thermo couple technical indicators:

Thermal Couple Accuracy (25℃)

Signal typeSensor range range (℃)accuracy (25℃)Heating drift (per ° C)
millivolt-100mV ~ +100mV±0.03mV±0.002 mV
B500  ℃ ~ 1810℃±0.77℃±0.075℃
E-200  ℃ ~ 1000℃±0.30℃±0.03℃
J- 190  ℃ ~ 1200℃±0.40℃±0.02℃
K-200℃ ~ 1372℃±0.40℃±0.0375℃
N- 190℃ ~ 1300℃±0.50℃±0.0225℃
R0℃ ~ 1768℃±0.75℃±0.0345℃
S0  ℃ ~ 1768℃±0.70℃±0.0345℃
L-200℃ ~ 800℃±0.5℃±0.0375℃


NCS-TT105 Temperature Transmitter Basic Parameter:


Input Signal

PT100、PT50_GOST、PT100_GOST、PT1000、PT200、PT500、CU50、CU50_GOST、CU100、CU100_GOST、0~500Ω、0~4000Ω;

B E J K N R S T L thermocouple, -100mV~100mV

RTD mode of connection

2,3,4 wires connection

Power

FF/PA

(9~32)VDC  19mA

HART

(11.5~45)VDC

Bus protocol

(4~20)mA+HART, FF, PA

Channels

2 channels

Insulation

1000VAC

Display

LCD LCD display or no display (optional)

Temperature Range

Operating temperature of the transmitter body:

(-40~85) ℃ (no display)

(-20~70) ℃ (with display)

Humidity Range

(5~95)%RH

Storage Temperature

-40 ~ 85℃

Start Time

≤5-Second Time (HART)

≤8-Second (FF, PA)

Refresh Time

The 0.8 ~ 1.3s depends on the type and wiring mode of the sensor

Damping Adjustment

Time constant of 0 to 32 seconds

Cold-end Temperature

±0.5℃

Alerting signal

(only HART)

The alarm output can be set at 3.5 … 23 mA

Upper / lower limit current 20.8mA / 3.8mA

Current accuracy

(only HART)

0.03%

Voltage Influence

±0.005%/V

Ex Level

Ex ia IIC T4 Ga (developed according to this standard, not certification)






Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right