NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter
- Microcyber
- China
- In Stock
- 500 Sets/Month
The NCS-TT306HR1 Series Intelligent Temperature Transmitter is a dual-channel DIN-rail mounted temperature transmitter featuring high reliability, high long-term stability, high precision, and low temperature drift. Equipped with advanced diagnostic functions, it is designed to meet the measurement requirements of critical process stages, making it an indispensable field device for process control.
1. Single-channel RTD/TC/Ohm/mV to 4-20mA & HART
2. NE107 compliant sensor & hardware fault detection
3. Certified to SIL2/SIL3 per IEC 61508 standard
NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter Product Overview
NCS-TT306H series HART temperature transmitter is a high-precision, low-temperature drift, andhigh-reliability product, including head-mounted NCS-TT306H and rail-mounted NCS-TT306H-R. It isindispensable in process control. Field equipment. The device integrates a wealth of functional modules,which can not only implement general detection functions, but also implement complex control strategies.
NCS-TT306H adopts digital technology and can be applied to a variety of thermal resistance andthermocouple sensors. It has a wide range and a simple interface between the field and the control room,and can greatly reduce installation, operation and maintenance costs.
NCS-TT306H series temperature transmitter supports 4-20mA+HART protocol and LCD display, andcan be widely used in petroleum, chemical, electric power, metallurgy and other industries.
NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter Features
Functional Safety (SIL):Certified to SIL2/SIL3 levels compliant with the IEC 61508:2010 standard, ensuring maximum reliability for critical safety instrumented systems.
Dual-Channel Versatility:Features a 6-terminal dual-channel design supporting various RTD, thermocouple, resistance, and voltage signals with flexible input combinations.
Exceptional Precision:Features transmitter-sensor matching technology for enhanced system accuracy, achieving ±0.1℃ (digital) for Pt100 and 0.03% analog output accuracy.
Advanced Diagnostics:Compliant with NAMUR NE107 standards, supporting comprehensive sensor and hardware fault detection for predictive maintenance and troubleshooting.
Seamless System Integration:Provides comprehensive EDD, FDI, and DTM device description files, ensuring full compatibility with various DCS systems.
Safety: complies with intrinsic safety requirements for secure operation in hazardous areas.
NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter Dimension

NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter wiring diagram:

Installation
Fix the temperature transmitter to the temperature housing or guide rail through the positioning holes with two screws.


NCS-TT306H-R1 Rail Mounted HART Temperature Transmitter Technical Specifications
Bus Interface | 4~20mA (supports current reversal) + HART 7 (supports BURST mode) |
Bus Power | 10~45 VDC / 10~30VDC (Intrinsic Safety/SIL) |
Wiring Method | 2, 3, 4 wire |
Input Signal | Resistance: 0~500Ω, 0~2000Ω, 0~4000Ω, 0~8000Ω |
Protocol Version | HART 7 |
Number of Channels | Dual channel |
Input Impedance | ≥10MΩ |
Electrical Isolation | 2kVAC / 50VAC |
Voltage Effect | ±0.005%/V |
LCD Display | Head mounted: supports LCD display or no display (optional) |
Key Operation | Support button setting parameters |
Working Temperature | -40(-55) ~ 85℃ (with display) |
Humidity Range | (5~95) %RH |
Storage Temperature | -40 ~ 85℃ |
Start Time | ≤10 seconds |
Update Time | 0.8 ~ 1.3s |
Damping Adjustment | Time constant 0~32 seconds |
Alarm Signal | Saturation lower limit: [3.75-4.0)mA, default 3.8mA |
Current Accuracy | 0.05% |
Terminal Torque | 0.4Nm |
Wire Specifications | 1.5mm² |
Anti-vibration Specifications | 2-25Hz: ±1.6mm; 25-100Hz: ±4g |
Protection Level | Terminal IP00, module housing IP20 |
Weight | Module ≤ 75g; graphics card: ≤50g |